Setup

2.1 Mounting the Controller

If necessary, the rear connector assembly may be removed from the main case for wiring (see Figure 2.1a for Square Mount, Figure 2.1b for Round Mount).

Square Mount Micro Controller Mounting Instruction

Figure 2.1a - Mounting the Square Mount Controller

Round Mount Micro Controller Mounting Instructions
1. Separate the display from the meter by squeezing the case (where shown) and then unplugging the cable from the meter.

2. Slide the retainer over the rear of the case, but do not engage serrations on case.

3. Pass the cable (from the display) thru a 1 3/4" diameter hole in the mounting panel and connect to the meter (take care to center the connector on the mating pins). While squeezing the case, press the display and meter squarely together until they connect.

4. Check the display and gasket for proper alignment, then slide the retainer tight against the backside of the mounting panel.

Figure 2.1b
Mounting the round mount controller
2.2 Front Panel View

Figure 2.2
Front Panel Display
Front Panel Annuciators
SP1
Setpoint 1 indicator
SP2
Setpoint 2 indicator
C
Alarm 1 indicator
AL2
Alarm 2 indicator
░C
░C unit indicator
░F
░F unit indicator
PV
Upper display shows the Process Value
SV
Lower display shows the Set Point Value
MENU
Changes display to Configuration Mode and advances thru menu items*
/MAX
Used in program mode and peak recall*
/MIN
Used in program mode and valley recall*
ENTER
Accesses submenus in Configuration Mode and stores selected

2.3 Rear Panel View

Figure 2.3 Typical Rear Connector Label and Possible Labels of Different Models

Rear Panel Connector Labels CE Approval Pending for solid relay (SSR) Option
POWER
AC Power Connector: All models
INPUT
Input Connector: All models TC, PR (Process) RTD
ALARM 1
ALARM 1 relay SPST, programmable: All models
OUTPUT 1

Control Output 1: Based on one of the following models.
Relay SPDT, Voltage and Current, Solid State Relay ,Pulse.

OUTPUT 2
Control Output 2: Based on one of the following models:
Relay SPST Normally Open, Solid State Relay, Pulse.
OPTION
Based on one of the following models:
RS232C, Isolated Analog Out, RS485, Alarm 2 Relay SPST, programmable, Remote Setpoint

2.4 Mechnical Installation

Dip Switch Configuration
The settings of the DIP switch must be verified or set to comply with your selection at the Input/Type menu (see Section 3.0 for Input/Type). The DIP switch is accessible through an opening on the side of the case. After carefully removing the controller from the case, see Section 2.1 for instructions, locate the dip switch (see Figure 2.4) and set the switches according to the following tables.

Figure 2.4 Dip Switch settings are shown in OFF position

Dip Switch Settings


2.5 Electrical Installation

POWER CONNECTION EXAMPLES
Caution The Productive Conductor terminal must be connected for safety reasons
FUSE
Connector
Output Type
For 110Vac
For 230Vac
FUSE 1.
Output 1
Realy
5A(T)
3A(T)
FUSE 2.
Output 2
Realy
5A(T)
3A(T)
FUSE P.
Power
N/A
50mA(T)
100mA(T)
FUSE A.
Alarm 1
Relay
3A(T)
3A(T)
Note: This Installation of fuses is optional, depending on level of protection required. Values shown are minimum recommendations for the protection of the controller. For a specific load, consult the respected electrical specification to select a suitable.

2.5.1 Thermocouple

Figure 2.5.2
Thermocouple Wiring Hookup
INPUT CONNECTION EXAMPLES

The figure below shows the wiring hookup for any thermocouple type. For example, for Type K hookup, connect the yellow wire to the + (+S) terminal and the red wire to the û (ûS) terminal. When configuring your controller, select Thermocouple and Thermocouple type in the Input Type menu (see part 3).

2.5.3 Two/Three-Wire RTD
The figures below show the input connections and input connector jumpers required to hookup a 2, 3 or 4-wire RTD.
The two-wire connection is the simplest method, but does not compensate for lead-wire temperature change and often requires calibration to cancel lead-wire resistance offset.
The three-wire connection works best with RTD leads closely equal in resistance. The controller measures the RTD, plus upper and lower lead drop voltage and the subtracts twice the measured drop in the lower supply current lead producing excellent lead-resistance cancellation for balanced measurements.
The four-wire RTD hookup is applicable to unbalanced lead resistance and enable the controller to measure and subtract the lead voltage which produces the best lead-resistance cancellation.

When configuring your controller, select RTD type and RTD value in the input .Type menu (see part 3)

2.5.4 Process Current

Figure 2.5.4 Process Current Wiring Hookup
The figure shows the wiring hookup for process current 0- 20mA.

When configuring your controller, select Process type in the Input Type menu (see part 3)
.

2.5.5 Process Voltage

Figure 2.5.5 Process Voltage Wiring Hookup
The figure shows the wiring hookup for process voltage 0 - .1V, 0 - 1V, 0 - 10V.

When configuring your controller, select Process type in the Input Type menu (see part 3).
Help Price List Specifications Print Manual Manuals Home
 Home Home  Table of Contents TOC  Back Back  Next Next